Can't Find Your Part? Enter Your NSN or PART Number Here:

Last Modified: Mar 21, 2019

NSN 5925-00-001-5914 Circuit Breaker

MFG Part Numbers: 402023-1, 3363-20-208VAC60HZCURVE2, 3363-20-250-60-2, 11900289, 3363-20-208VAC60HZCURVE2, 3363-20AMP

Cross Reference Parts for NSN 5925-00-001-5914

MFG Part Number ISC RNVC RNCC HCC MSDS SADC DAC

402023-1

2 9 5 A

3363-20-208VAC60HZCURVE2

2 2 3 5

3363-20-250-60-2

2 9 5 E

11900289

2 9 5 5

3363-20-208VAC60HZCURVE2

2 2 3 5

3363-20AMP

2 2 5 5

Request A Quote

Part:
Qty:
Email:

Part Information for NSN 5925-00-001-5914 (5925000015914)

Item Name: CIRCUIT BREAKER
Federal Supply Class (FSC): 5925
NIIN: 00-001-5914 (000015914)
Definition: A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. may include provisions for manual operation. at least one set of contacts must be in series with the actuating element(s). a combination of semiconductor and passive devices may be used in lieu of contacts. for automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). for items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. excludes circuit breaker box and magneto "breaker" assemblies. see also switch (as modified); and controller.
NMF Description: CIRCUIT BREAKER/SWITCH NOI

Item Specifics

Federal Supply Class (FSC)
Circuit Breakers
Actuator Function
Trip-reset CPRW
Actuator Position Designation
At pole two CPRX
Body Height
2.687 inches nominal ADAU
Body Length
5.250 inches nominal ADAQ
Body Style
Multipole-single actuator type AAQL
Body Width
3.000 inches nominal ADAT
Boss Height
0.219 inches nominal AJEC
Case Material
Plastic ADTV
Center To Center Distance Between Terminals Parallel To Length
4.359 inches nominal AEBP
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal AEBQ
Circuit Protection Type
Overcurrent all locations CPRH
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.000 inches nominal AEHA
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.359 inches nominal AEBY
Frequency In Hertz
60.0 all locations FREQ
Arc Quenching Method
Magnetic blowout APNQ
For Use With/On
Asr7 AGAV
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations CPLM
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations CPRG
Mounting Facility Type And Quantity
4 unthreaded hole AXHR
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations CPRF
Storage Type
General purpose warehouse BBRG
Unpackaged Unit Weight
1.875 pounds PKWT
Inclosure Protection Type For Which Designed
Fungus resistant and moisture resistant CQXF
Internal Trip Release Configuration
Series trip all locations CPSM
Main Contact Tripping Mechanism Type
Trip free CPRR
Manual Actuator Type And Quantity
1 toggle CPRT
Reset Method
Manual CPRQ
Pole Quantity
3 AKPX
Terminal Type And Quantity
6 compression TTQY
Trip Delay Time In Seconds Per Rated Continuous Current
13.000 minimum at 150 pct all locations and 45.000 maximum at 150 pct all locations and 5.500 minimum at 200 pct all locations and 19.000 maximum at 200 pct all locations CQWN
Trip Release Characteristic
Time delay all locations CPRL
Trip Release Method
Magnetic-hydraulic all locations CPRJ
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations CPRN
Unthreaded Mounting Hole Diameter
0.190 inches nominal AEBV

Trade Control Compliance Schedule B Export Code: A ten position numeric code that identifies an item exported overseas. this unique identification code is assigned by the U.S. Census Bureau.

Schedule B Sch. B Description Demilitarization Classification ITAR Regulation
8536200040 Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi Non-usml/non-ccli - no demil or dod tsc required. department of commerce may impose licensing requirements to certain destinations. (note 9). Unclassified Not ITAR Controlled

MOE / End Users Represents the subdivisions of a US governmental organization or an agency of the North Atlantic Treaty Organization (NATO), and other friendly governments and international organizations participating in the federal catalog program.

Country / Entity Name MOE
ZZ Federal Aviation Administration ZZ

Material & Special Handling Item material and handling information

Code Description Value Meaning
HMIRS P Indicates there is no information in the hmirs. the nsn is in a fsc in table ii of fed std 313 and a msds may be required by t
Precious Metals Indicator U Precious metal content is unknown
Criticality Code N The item does not have a critical feature such as tolerance, fit restrictions or application. nuclear hardness properties have not been determined (not valid for input).

National Motor Freight NMFC: A six position numeric code, which divides articles into groups or classes according to physical characteristics. The classification is based on truckloads vs. less than truckload.

Code Description Code Value Meaning
NMF Description NMFC 061300 Circuit Breaker/switch Noi
Less than a truck load rating LTL P 77.5
Water Commodity WCC 658 Electrical appliances, small
Type of Cargo TCC Z No special type of cargo code applicable
Special Handling SHC 9 Other or no special handling required (sh)
Air Dimension Code ADC A Shipment is not a consolidation and does not exceed 84 inches in any dimension.
Air Commodity ACC H Instruments/equipment/supplies for radio, communications, electrical, laboratory, etc. (includes signal corps)
Air Special Handling ASH Array No special handling required.

Item Identification | Circuit Breakers

5925-00-001-5914, A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. may include provisions for manual operation. at least one set of contacts must be in series with the actuating element(s). a combination of semiconductor and passive devices may be used in lieu of contacts. for automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). for items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. excludes circuit breaker box and magneto "breaker" assemblies. see also switch (as modified); and controller.

Supply Class (FSC)NSN AssignmentNIINItem Name Code (INC)
5925 Sep 29, 1972 000015914 00136 (Circuit Breaker)

Circuit Breakers Cross Reference

3363-20-208VAC60HZCURVE2 Cage Code 08125
402023-1 Cage Code 96214
11900289 Cage Code 82796
3363-20-208VAC60HZCURVE2 Cage Code 74193
3363-20AMP Cage Code 74193
3363-20-250-60-2 Cage Code 74193

Codes

COUNTRY CODE: 00
CIIC: U
DML: A
HMIC: P
MGMT CTRL: -------
SOS: G69
INC: 136
AAC: G
CRITL CODE: N
DEMIL CODE: A
S A: GE
MGMT CTL: -------
NIIN ASGMT: 29-SEP-72
QUP: 1
SLC: 0
UI: EA
CAGE: 74193
RNCC: 5
RNVC: 9
Similar parts: 5925-00-259-5682 5925-00-257-9116 5925-00-259-3927 5925-00-259-7485 5925-00-258-5049 5925-00-262-5672 5925-00-254-9416 5925-00-261-7702 5925-00-258-8278 5925-00-259-2096 5925-00-259-4614